한국과 일본의 자동화재 탐지설비의 화재안전기준 비교연구
Comparative Study on the National Fire Safety Codes of Automatic Fire Detection System in Korea and Japan
공하성 ( Ha Sung Kong ) , 조태재 ( Tae Jea Cho ) , 하헌우 ( Hun Woo Ha )
UCI I410-ECN-0102-2012-550-001660239

The efforts and study to improve the problems to the automatic fire detection system in Korea continues now. This study, by comparing and analyzing the standard of the automatic fire detection system in Korea and Japan, presents the improvements to limit an installation of analog type detector among projected beam type smoke detector and air sampling-type detector at more than 20m for the attachment height, recommend on installing the control panel of P-type third degree in the individual house and the apartment house, revise that the manual fire alarm box and sound equipment shall be installed satisfied with both of below 25m of horizontal distance and 50m of walking distance, introduce sound alarm type at the large buildings and correct the transmission and distribution of electricity type into two wire detector among the terms on wiring.